Retrofit of the Washington Plaza backup power plant
Intervention type
Product definition, commissioning assistanceCustomer
GENINGDate of completion
Location
Paris, FranceContext
The Washington Plaza is a business center located in Paris. Its electrical installation comprises several redundant high-voltage (HV) distribution substations, with automatic changeover managed by a centralized technical management system (CTM). The emergency power station comprises two 1500 kVA generators, in parallel to supply the low-voltage switchboard (LVS) in change over mode.
The backup power plant, installed in 1991, requires modernization. The purpose of the renovation project is to replace the original electromechanical control systems, as well as the old Renault electronic boards, using a more efficient automated system.
Application type
The project concerns a change over application, where two gensets (GE) are used to ensure continuity of power supply in case of main electrical grid failure. In this application, the transfer switch is not managed by CRE Technology controller.
Energy sources
- Gensets: 2 x GE Cummins KTA50 G2, 1500 kVA each, synchronized for a total output of 2.4 MW.
- Alternators: Leroy Somer AA 50 L10 with AVR RS128-0 voltage regulator.
Application details
The GENSYS COMPACT PRIME is used for paralleling and synchronizing of generator sets. In the event of an outage on the main grid, these two devices automatically start the generators via a command from the BMS. After paralleling, they supply the TGBT in emergency mode. The GENSYS COMPACT PRIME also provides automatic power management, starting or stopping the gensets according to load.
When the mains return, the CTM deactivates the command, and the mains resumes the load, while the GENSYS COMPACT PRIME executes the engine stop sequence.
An i4GEN 10" color touchscreen was installed to supervise the entire installation, facilitating management of the two generators.
Service provided by CRE
CRE Technology supported the commissioning of this installation, contributing to a safe transition to the new automated system.
Products installed
- 2 x GENSYS COMPACT PRIME
- 1 x i4GEN 10’’
- 2 x generator battery chargers BPRB2024M
Related products
GENSYS COMPACT PRIME
The GENSYS COMPACT PRIME is designed for advanced management of multiple generators in power plants, while offering interoperability with other types of energy sources for more complex systems.
Add to quoteBPRB chargers
Medium power chargers with a wide AC input voltage range and advanced functions
Add to quote